Current transformer TI-150

Current transformer TI-150

TI-150-5, 5908312594963

Product description

150/5 transformer. 2,5 VA.
The current transformer is used for proportional change of high current strength to lower values, adapted to the measuring range of control and measuring devices.

Functioning
The cable with the measured current passes through the main opening of the transformer (P1 / P2), which is equivalent to one coil of the primary winding. The S1 and S2 terminals of the secondary windings are connected to the terminals of the measuring circuit of the control or measuring device.
The ratio of the strength of the currents in both windings is a constant value and is called the current ratio: IPn/ISn=N, where the IPn is rated primary current; ISn - rated secondary current; N - the value of the transmission. The value of the current flowing through the primary winding can be determined from the value of the current flowing through the secondary winding: ISm*N=IPm, wherein ISm - measured primary current; IPm - measured secondary current.
        

Please note!
It is recommended to connect the secondary circuit by a wire with diameter of not less than 2.5 mm².
It is recommended to ground the S2 terminal.
It is prohibited to disconnect the secondary circuit during operation of the transformer (the high voltage that may appear pose a risk of electric shock to the people or damage to the device).


     

 

Typesingle-phase
Buildingwith close core
Transmission lp / ls150/5
Class0,5
Power [VA]2,5 VA
Frequency50÷60 Hz
Maximum working voltage0,66 kV AC
Standard numberIEC 60044-1
Nominal secondary current Is5 A
Isolation breakdown voltage3 kV/1 min.
Weight0,235 kg
Security factorFS Ë‚ 5
Connection S1 / S2zaciski śrubowe 4 mm²
Opening dimensions P1 / P2 - A1 / A2 / A3xB; C [mm]30 mm/25 mm/20 mm x 10 mm; Ø22 mm
Dimensions WxHxD [mm]61 mm × 81 mm × 34 mm
Tightening torque0,5 Nm
Working temperature-5÷40°C
Mounting positionvertical/horizontal
Assemblyblackboard / busway
Ingress Protection MarkingIP20







typeIp/Isclasspower  
[VA]
hole dimensions P1/P2
A1/A2/A3×B; C [mm]
dimensions
W×H [mm]
weight
[kg]
TI-30* 30/5 12,5Ø2244×67×300,135
TI-4040/511Ø22 44×67×300,135
TI-5050/511,5Ø22 44×67×300,135
TI-6060/511,5Ø22 44×67×300,135
TI-7575/5 11,5Ø2244×67×300,135
TI-8080/511,5Ø22 44×67×300,135
TI-100 100/5  0,5
2,530/25/20×10; Ø2261×81×34 0,235
TI-150150/50,52,530/25/20×10; Ø22 61×81×34 0,235
TI-200200/50,55,030/25/20×10; Ø22 61×81×34 0,235
TI-250250/50,55,030/25/20×10; Ø22 61×81×34 0,235
TI-300300/5 0,55,030/25/20×10; Ø2261×81×34 0,235
TI-400400/5 0,51040/30/ - ×10; Ø30 75×99×40 0,305
TI-600600/50,51040/30/ - ×10; Ø30 75×99×40 0,305
TI-10001000/5 0,51062/52/38×21; Ø46126×102×62-
TI-12501250/50,51062/52/38×21; Ø46 126×102×62-
TI-16001600/5 0,51062/52/38×21; Ø46126×102×62-


Attention! 
Applies only to TI-30

* For correct operation of the transformer, a 4-fold transmission of the current cable through the transformer's opening is required.