PR-602, 5908312595939
Functioning
The potentiometer sets the value of drawn current (from 2A to 15A; for PR-615: from 4A to 30A) in the priority circuit, above which the receiver cuts off the non-primary circuit. A drop in current consumption in the priority circuit below the set threshold value will result in an automatic activation of the non-priority circuit. In cases where the priority receiver is already activated, the priority relay will prevent the activation of the non-priority receiver.
Attention!
Circuits equipped with master relays require over-current security devices with increased actuation time, in order to prevent them operating before actuation of the relay.
Availability date:
Type | direct connection |
Power supply voltage | 230 V AC |
The executive element | relay |
Contact configuration | 1 × NO |
Separation of the contact | YES |
Maximum current of non-priority receivers | 16 A or larger contactor |
Maximum current of priority receivers | 15 A |
Switching current | 2÷15 A |
Switching delay | 0,1 s |
Return delay | 0,1 s |
Power return hysteresis | 10% |
Terminal | pluggable terminal blocks 4,0 mm² |
Tightening torque | 0,5 Nm |
Power consumption | 0,4 W |
Working temperature | -25 ÷ 50 °C |
Dimensions | 51×67×26 mm (± 1 mm) |
Assembly | on wall |
Ingress Protection Marking | IP20 |