Timing relays PCR-513-16

Timing relays PCR-513-16

PCR-513-16, 5902431672083

Product description

Timing relays are devised to time the control of industrial and domestic automatic control engineering systems (e.g. ventilation, heating, lighting, signalling, etc.).
Operation mode: Lagged activation.

Functioning
After the power voltage is supplied, the contact remains in position 11-10 and the timing of the preset value t is commenced. After the preset time t has been counted down, the contact is shifted to position 11-12. The working sequence of the relay may be repeated after turning the power supply off and on.

 


 

Attention!
* Setting the time range knob regulator in the:
  ON - position with power supply activated results in the permanent closure of the contact in position 11-12.
  OFF - position (power supply activated) causes the contact to be permanently closed in the 11-10 position.
* With the power supply on, the system does not respond to time range setting modifications.
* The newly set time range is active after the power supply has been turned off and on.
* With the power supply on, it is possible to regulate the preset time freely within the selected time range.

 

Power supply voltage230 V AC
Operating modelagged activation
The executive elementrelay
Maximum load current16 A
Contact configuration1 × NO/NC
Separation of the contactYES
Contact status indicationLED red
Operating time - adjustable0,1 s ÷ 576 godz.
Power indicationLED green
Terminalpluggable terminal blocks 2,5 mm²
Tightening torque0,4 Nm
Power consumption0,8 W
Working temperature-25 ÷ 50 °C
Dimensions1 module (18 mm)
Assemblyon rail 35 mm
Ingress Protection MarkingIP20