Electronic bistable impulse relay BIS-419i 24 V

Electronic bistable impulse relay BIS-419i 24 V

BIS-419i 24 V

The electronic bistable relay enables switching on the lighting or other device from several different points by means of parallel connected control buttons.
Sequential. Power supply 24V AC . Maximum load 2 x 16 A (160 A / 20 ms). On the 35 mm rail.

Electronic bistable pulse relay enables switching on or off the lighting or other device from several different points by means of parallel connected, momentary (bell) control switches.

The BIS-419 relay has two switching sections and enables two circuits (branches) of lighting or other receivers to be connected according to the selected sequence from several different points.
 

Functioning
Power supply of the relay is signaled by the green LED. The sequential relay has two separate outputs R1 and R2. The contact status (closed / open) is forced sequentially according to the given program. Switching the contacts into the next state follows the next pulse of the control button. Switching on contact R1 and R2 is signaled by lighting of the corresponding red LEDs R1 and R2. After a power failure, the contact status is reset. After restarting the supply voltage, the relay starts operation from sequence No. 0.
 

Work functions

Function A


 
   

Subsequent presses of the button repeat sequence 0-3.
 

Function B

* Repeatedly pressing the button in less than 5 seconds, repeats sequences 1-3.
* The next pressing of the button after a time longer than 5 s, disconnects both contacts (sequence 0).
* Long press of the button - in any sequence - disconnects both contacts (sequence 0).
* After switching off both relays, pressing the button again restores the state before the shutdown (state memory). It does not apply to the case of power failure of the relay.
 

Function C

Subsequent presses of the button repeat sequence 0-3.
 

Function D


 

* Repeatedly pressing the button in less than 5 seconds, repeats sequences 1-3.
* The next pressing of the button after a time longer than 5 s, disconnects both contacts (sequence 0).
* Long press of the button - in any sequence - disconnects both contacts (sequence 0).
* After switching off both relays, pressing the button again restores the state before the shutdown (state memory). It does not apply to the case of power failure of the relay.
  

Power supply voltage9├Ě30 V AC/DC
Local controlYES
Maximum AC-1 load current2 x16 A (160 A/20 ms)
The executive elementrelay
Contact configuration2 ├Ś NO
Separation of the contactYES
Resistance to shock currentsYES
Number of channels2
functionalitysequential
Delay of operation0,1 ├Ě 0,2 s
Control pulse currentless than 1 mA
Cooperation with illuminated buttonsYES
Tightening torque0,4 Nm
Working temperature-25 ├Ě 50 ┬░C
dimensions1 module (18 mm)
Assemblyon rail 35 mm
Level of securityIP20
Przyciski pod┼Ťwietlane
Z uwagi na niskie napi─Öcie zasilania nie nale┼╝y stosowa─ç przycisków pod┼Ťwietlanych.

Maksymalny pr─ůd obci─ů┼╝enia
Pr─ůd styku podany w danych technicznych jest warto┼Ťci─ů maksymaln─ů i mo┼╝e podlega─ç ograniczeniom – wi─Öcej informacji. Je┼Ťli z przedstawionych informacji wynika, ┼╝e przeka┼║nik w urz─ůdzeniu jest niewystarczaj─ůcy zaleca si─Ö stosowa─ç zewn─Ötrzny element prze┼é─ůczaj─ůcy (np. stycznik) przystosowany do prze┼é─ůczania du┼╝ych pr─ůdów udarowych.


Pami─Ö─ç stanu
Przeka┼║nik nie posiada "pami─Öci" pozycji styku. Oznacza to, ┼╝e po za┼é─ůczeniu zasilania styk przeka┼║nika zawsze pozostanie w stanie wy┼é─ůczonym.

Odporno┼Ť─ç na pr─ůdy udarowe
W urz─ůdzeniu zastosowany zosta┼é przeka┼║nik typu "inrush" charakteryzuj─ůcy si─Ö du┼╝─ů wytrzyma┼éo┼Ťci─ů na krótkotrwa┼ée pr─ůdy udarowe powstaj─ůce np. w momencie za┼é─ůczenia lamp LED, ┼Ťwietlówek ESL, tranformatorów elektronicznych, lamp wy┼éadowczych itp.