MB-DS-30 Temperature Transmitter
search
  • MB-DS-30 Temperature Transmitter
  • MB-DS-30 Temperature Transmitter
  • MB-DS-30 Temperature Transmitter

MB-DS-30 Temperature Transmitter

MAX-MB-DS-30, 5902431673912

Multi-point temperature transducer with Modbus RTU communication.
Up to 30 external DS18B20 digital temperature sensors.
Sensor bus: 1-Wire.
Measuring range: −55 to 125°C.
System interface: RS-485.
Temperature sensors must be selected separately.

MB-DS-30 Multi-point Temperature Transmitter, Modbus RTU

Why choose the MB-DS-30?

The MB-DS-30 enables temperature measurement at up to 30 points using external DS18B20 digital sensors operating on the 1-Wire bus. The results are available via RS-485 Modbus RTU.

What does this mean in practice?

  • Support for up to 30 measurement points.
  • Compatibility with DS18B20 digital temperature sensors.
  • The sensor bus operates on the 1-Wire standard.
  • The measurement range is −55 to 125°C.
  • The current temperature of the connected sensors can be read.
  • Measurement and communication parameters are accessible via RS-485 Modbus RTU.
  • The dedicated SDS1 probe is sold separately.

MODBUS RTU PROTOCOL PARAMETERS

FF MB-DS-30 rejestr 1.gif


REGISTERS

Przetwornik temperatury MB-DS-10 rejestry


MB Config service programme

Service programme for quick configuration of the module’s communication and operating parameters, and for addressing DS sensors.
The programme is available on the device’s subpage or in the DOWNLOADS tab on the website www.fif.com.pl

MBConfig_DS-30.gif

1-WIRE Standard

The MB-DS-10 utilises a single-channel 1-Wire Master circuit, which enables impedance matching and active ‘intelligent’ pull-up. It enables the construction of small and large 1-Wire networks in serial, hub and star topologies with a length or radius of up to 500 m.
For more information, see the links below:
https://www.maximintegrated.com/en/design/technical-documents/tutorials/1/148.html

https://datasheets.maximintegrated.com/en/ds/DS2482-100.pdf



 

MAX-MB-DS-30
Power supply voltage
9÷30 V DC
Communication protocol
MODBUS RTU
Stop bits
1 / 1.5 / 2
Measurement range
-55÷125°C
ports
RS-485
Temperature probe
DS1820 lub DS18B20
Reading accuracy
-10÷85°C: ±0,5°С, -55÷-10°C/-85÷125°C: ±2,0°С
The type of work
SLAVE
Baudrate
1200÷115200 bit/s
Data bits
8
Bits of parity
EVEN / ODD / NONE
Address
1÷247
Maximum measuring error
±1°C
Terminal
pluggable terminal blocks 2,5 mm²
Tightening torque
0,4 Nm
Power consumption
0,3 W
Working temperature
-20÷50°C
Dimensions
1 module (18 mm)
Assembly
on rail 35 mm
Ingress Protection Marking
IP20


You might also like Products