AC-1I 5A analogue current transducer
search
  • AC-1I 5A analogue current transducer
  • AC-1I 5A analogue current transducer
  • AC-1I 5A analogue current transducer

AC-1I 15A current transducer

MAX-AC-1I-15A, 5908312595250

An analogue current transducer with a 4–20 mA current output.
Measurement input: 0–15 A AC / 0–20 A DC.
Direct measurement.
True RMS measurement


AC-1I 15A current transducer, 4–20 mA output

Why choose the AC-1I 15A?

The AC-1I 15A is designed for the direct measurement of alternating or direct current. The measured value is converted into a 4–20 mA analogue current signal.

What does this mean in practice?

  • The current measurement input operates within the range 0–15 A AC / 0–20 A DC.
  • The measurement is taken directly, without the need for a current transformer in the device’s input range.
  • True RMS measurement is performed.
  • The measurement result is available as a 4–20 mA analogue current signal.
  • The output is fitted with an anti-interference filter.
  • The maximum length of the signal cable is 300 m.

MAX-AC-1I-15A
Power supply voltage
9÷30 V DC
WE-WY breakthrough voltage
2,1 kV
Maximum measuring error
±0,2 A
Output signal
4÷20 mA
Processing error
±0,5%
The length of the signal output wire
300 m
Measurement range TrueRMS / maximum voltage
0÷15 A/285 V AC; 0÷20 A/400 V DC
Permissible overload
100 A/100 ms
Terminal
pluggable terminal blocks 2,5 mm²
Tightening torque
0,4 Nm
Power consumption
0,8 W
Working temperature
-20÷50°C
Dimensions
1 module (18 mm)
Assembly
on rail 35 mm
Ingress Protection Marking
IP20