MB-AHT-3 – RS-485 Modbus RTU temperature and humidity transducer
search
  • MB-AHT-3 – RS-485 Modbus RTU temperature and humidity transducer
  • MB-AHT-3 – RS-485 Modbus RTU temperature and humidity transducer
  • MB-AHT-3 – RS-485 Modbus RTU temperature and humidity transducer

MB-AHT-3 – RS-485 Modbus RTU temperature and humidity transducer

MB-AHT-3, 5902431679419

The MB-AHT-3 is a temperature and relative humidity sensor with an RS-485 interface and Modbus RTU protocol. It enables continuous measurement of environmental parameters and allows these to be read by building and industrial automation systems. The device takes measurements approximately every 1 second, records minimum and maximum values, and allows for remote configuration of communication parameters. Designed for wall mounting or mounting on a junction box.

Intended use

The MB-AHT-3 is an electronic measuring transducer designed for the continuous monitoring of temperature and relative humidity. The device is equipped with an RS-485 communication interface, enabling the transmission of measurement data via the Modbus RTU protocol.

The transmitter can be used in building automation and industrial systems where real-time temperature and humidity readings are required, and where this information needs to be transmitted to a master monitoring or control system.

The MB-AHT-3 takes measurements approximately every 1 second. In addition to real-time readings, it provides the minimum and maximum recorded values for both parameters, information on operating time and the device status.

Thanks to its configurability via the RS-485 bus, the transducer can be adapted to the communication parameters of the installation. The settings are stored in non-volatile FLASH memory, which ensures they are retained even when the power is switched off.

Functions and capabilities of the MB-AHT-3 transducer

  • Temperature and relative humidity measurement – simultaneous monitoring of two environmental parameters using a single device.

  • RS-485 Modbus RTU communication – reading measurement data and configuring the transducer via the communication bus.

  • Measurement updates approximately every 1 second – regular provision of information on air temperature and humidity.

  • Recording of minimum and maximum values – the ability to read the extreme temperature and humidity values since the last start-up or reset of the registers.

  • Software-based measurement correction – the ability to adjust temperature and humidity readings via Modbus registers.

  • Configurable communication parameters – setting the device address, baud rate, parity and number of stop bits.

  • Non-volatile FLASH memory – configuration is retained after a power failure.

  • LED indicators – provide information on the device’s operation and the transmission of Modbus responses.

  • Built-in 120 Ω terminating resistor – option to enable RS-485 bus termination via the TERM jumper.

  • Duplicate connection terminals – facilitate the connection of further devices to the communication bus.

Operation of the Modbus RTU temperature and humidity transducer

The MB-AHT-3 transducer periodically measures air temperature and relative humidity. The measured values are made available in Modbus RTU registers, enabling them to be read by a master device, e.g. a controller or monitoring system supporting this protocol.

The device provides the following information:

  • current air temperature;

  • current relative humidity;

  • minimum and maximum recorded temperature;

  • minimum and maximum recorded humidity;

  • operating time since the last start-up;

  • the device’s system status.

The minimum and maximum values and the operating time are stored in volatile memory. They are reset after a restart or when the power is switched on again. The minimum and maximum values can also be reset via the relevant Modbus register.

The transducer allows for the correction of temperature readings within a range of −10.0 to +10.0 °C and relative humidity within a range of −50.0 to +50.0%. Configuration changes are saved in non-volatile memory.

MB-AHT-3

The MB-AHT-3 temperature and humidity transmitter is powered by a voltage of 9–30 V DC. Communication with the device takes place via an RS-485 interface using the Modbus RTU protocol.
The device is equipped with an 8-position screw terminal block. Duplicated power supply and communication terminals allow for the convenient connection of additional devices to the RS-485 bus.

Terminal description

Terminal

Function

+

Power supply 9–30 V DC – positive terminal

−

Power supply – negative terminal (ground)

A

RS-485 communication – line A

B

RS-485 communication – line B


Note!
Ensure correct polarity when connecting the power supply. Exceeding a voltage of 30 V DC may damage the device.

Connection to the RS-485 bus

The MB-AHT-3 transducer can be connected to an RS-485 bus alongside other devices that support the Modbus RTU protocol.

In installations involving multiple transducers, ensure that the communication lines A and B are connected correctly, and assign a unique Modbus address to each device.

Appropriate termination must be applied at both ends of the RS-485 bus. The MB-AHT-3 is equipped with a built-in 120 Ω terminating resistor, which can be enabled using the TERM jumper located on the device's circuit board.

Configuration jumpers

Jumper

Function

TERM

Enables the 120 Ω terminating resistor between lines A and B

DEFAULT

Restores factory communication settings when the device is powered on with the jumper closed

Important: Disconnect the device's power supply before making any connections. RS-485 signal cables should be routed away from power cables and sources of electromagnetic interference.

The MB-AHT-3 temperature and humidity transmitter is configured via an RS-485 interface using the Modbus RTU protocol. It allows for the configuration of communication parameters, the correction of measurement readings, and the restoration of factory settings.

Configuration settings are stored in non-volatile FLASH memory, ensuring they are retained even after the power is turned off.

Default Modbus RTU communication parameters

Parameter

Factory value

Operating mode

Slave

Modbus address

1

Baud rate

9600 bps

Data bits

8

Parity

None

Stop bits

1

Communication parameter configuration

The MB-AHT-3 transducer allows for the modification of the device address, baud rate, parity, and the number of stop bits by writing to the corresponding Modbus registers.

Register

Parameter

Available settings

0x100

Modbus address

1÷245

0x101

Baud rate

1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 bit/s

0x102

Parity

None, Even, Odd

0x103

Stop bits

1 or 2


Note:
Changes to the baud rate, parity, or number of stop bits take effect immediately upon receipt of the command. After changing the parameters, the settings of the master device must be adjusted accordingly.

Temperature and humidity measurement correction

The MB-AHT-3 allows for software-based correction of measured values ​​via specific Modbus registers.

Register

Parameter

Correction range

0x080

Humidity correction

−50.0 to +50.0% RH

0x081

Temperature correction

−10.0 to +10.0 °C


The correction is saved with a resolution of 0.1 °C or 0.1% RH. After applying the correction, the humidity value is limited to the range of 0.0–100.0% RH.

How do I connect the MB-AHT-3 to an automation system?

The transducer must be powered with a voltage of 9–30 V DC, and the communication lines A and B must be connected to an RS-485 bus. The master system must support the Modbus RTU protocol and use communication parameters that match the device's settings.

What are the factory-default Modbus RTU communication parameters?

The default device address is 1, the baud rate is 9600 bps, and the data format consists of 8 data bits, no parity, and 1 stop bit. These parameters can be modified via the appropriate Modbus registers.

Does the MB-AHT-3 store minimum and maximum temperature and humidity values?

Yes. The device records the minimum and maximum temperature and humidity values ​​since the last startup or register reset. This data is stored in volatile memory and is lost when the power is disconnected.

Is it possible to calibrate or adjust the temperature and humidity readings?

Yes. The MB-AHT-3 allows for software-based adjustment of readings, with a setting resolution of 0.1 °C or 0.1% RH. These adjustments can be configured via the Modbus RTU bus.

How can I ensure accurate measurement conditions?

During installation, ensure the housing is oriented correctly and that the ventilation openings remain unobstructed. Do not block these openings with cables or other installation components, as free airflow is essential for obtaining reliable measurement results.