MB-3U-1 Voltage Transducer
search
  • MB-3U-1 Voltage Transducer
  • MB-3U-1 Voltage Transducer
  • MB-3U-1 Voltage Transducer

MB-3U-1 Voltage Transducer

MAX-MB-3U-1, 5908312595311

Three-channel AC/DC voltage transducer with Modbus RTU communication.
3 voltage measurement channels.
Range of each channel: 0–285 V AC / 0–400 V DC.
True RMS measurement.
Communication interface: RS-485.

MB-3U-1 three-phase voltage transducer, Modbus RTU

Why choose the MB-3U-1?

The MB-3U-1 is designed for continuous voltage measurement across three channels and data exchange via RS-485 in accordance with the Modbus RTU protocol. It can measure either AC or DC voltage.

What does this mean in practice?

  • The device has 3 voltage measurement channels.
  • The AC voltage measurement range is 0–285 V, and the DC range is 0–400 V.
  • True RMS measurement is performed.
  • The sampling frequency is 10 Hz.
  • The results for each channel are available via Modbus RTU.
  • The measurement channels are not galvanically isolated from one another.
  •  The measurement channels are galvanically isolated from the transducer’s power supply input and the RS-485 communication port. The RS-485 port is not isolated from the supply voltage.
  • AC and DC voltages must not be measured simultaneously.
  • Measurements of DC voltages are taken relative to a common supply point or GND.

Reset communication settings
A DIP switch is located beneath the module’s front panel.
Details on resetting are available in the manual.

MB Config
The programme allows you to test-read values and configure the transducer’s communication and configuration parameters.



Communication between the module and a PC via theCN-USB-485 USB converter
The programme is free of charge.

MAX-MB-3U-1
Power supply voltage
9÷30 V DC
Communication protocol
MODBUS RTU
Stop bits
02-sty
WE-WY breakthrough voltage
3 kV
ports
RS-485
The type of work
SLAVE
Baudrate
1200÷115200 bit/s
Data bits
8
Bits of parity
EVEN / ODD / NONE
Address
1÷247
Maximum measuring error
0,50%
Processing error
±0,5%
Measurement range TrueRMS - alternating AC voltage
0÷285 V
Measurement range TrueRMS - DC voltage
0÷400 V
Power consumption (max)
50 mA
Precision of reading the register
1 V
Sampling frequency
10 Hz
Relative air humidity (for 30
85%
Terminal
pluggable terminal blocks 2,5 mm²
Tightening torque
0,4 Nm
Dimensions
1 module (18 mm)
Assembly
on rail 35 mm
Ingress Protection Marking
IP20



Module in RS-485 network





Setting the network address




Measurement voltage




Reset communication settings

Communication parameters MODBUS RTU protocol